Installation & Operating Procedures
Opal LT
Series
RVS-AX Analogue Soft Starter
8-170A, 220V-600V
Manufactured By SOLCON
Vue de la page 0
1 2 3 4 5 6 ... 11 12

Résumé du contenu

Page 1 - Opal LT

www.safdrives.comemail: [email protected](Replies given within 24 hours)18 Neville Street, Unit CNew Hamburg, ON N3A 4G7Tel: 519-662-6489Fax: 1

Page 2

Technical Specification 9 Environment Supply voltage Three phase, line to line, 380 – 415 Vac +10% -15% 460 – 500 Vac +10% -15% * 575 – 600 Vac

Page 3 - Table of Contents

Dimensions \\SOLSRV1\Data\Catalogs and Marketing materials\Instruction Manuals\RVS-AX

Page 4 - Starter Selection

www.safdrives.comemail: [email protected](Replies given within 24 hours)18 Neville Street, Unit CNew Hamburg, ON N3A 4G7Tel: 519-662-6489Fax: 1

Page 5 - Installation Notes

Supplied By RRVVSS--AAXX AAnnaalloogguuee SSoofftt SSttaarrtteerr 88--117700AA,, 222200--660000VV

Page 6 - Reduced Voltage Starter

Table of Contents Page Subject 3 Starter Selection 4 Installation Notes 5 Wiring 6 Starter Settings 7 Motor Protection 8 Start-up Procedure 9 Tech

Page 7 - Starter Settings

Starter Selection 3The RVS-AX electronic soft starter incorporates six thyristors to start a three-phase squirrel cage induction motor. By supplyi

Page 8 - Motor Protection

Installation Notes 4Prior to Installation Check that Motor's Full Load Ampere (FLA) is lower than or equal to starters Full Load Current (FL

Page 9 - Startup Procedure

Wiring 5 Block and Connection Diagram NOTE: The RVS-AX incorporates an internal control voltage transformer connected

Page 10 - Technical Specification

Starter Settings 6Front Panel Layout 10% 50%Initial Voltage100% 400%Current Limit230 Sec.Ramp-Up 0.2 30 Sec.Ramp-DownFLC %50% 100%°°°°°°°°°°°°°°°

Page 11 - Dimensions

Motor Protection 7ominal current to 2 sec. at 600% of nominal urrent. en one or two phases are missing r more than 1 sec. op urate indication of

Page 12

Startup Procedure 81. Set FLC (Motor Full Load Current) - according to 2. Calculation: 100 LCStarter F Motor FLA FLC ×= 3. Set other pote